Corrective Action - Franklin Electric SubDrive Connect Serie Manual De Usuario/Instalador

Ocultar thumbs Ver también para SubDrive Connect Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

MAINTENANCE
Troubleshooting
Code Fault
F5
Open Phase
F6
Short Circuit
F7
Overheated Drive
F9
Internal PCB Fault
F12
Overvoltage
F14
Broken Pipe
F15
Phase Imbalance
F16
Ground Fault
F17
Inverter Tempera-
ture Sensor Fault
44
Possible Cause
• Loose connection
• Defective motor or drop cable
• Wrong motor
• When fault is indicated
immediately after power-up,
short circuit caused by a shorted
connection, defective cable,
splice or motor
• High ambient temperature
• Direct sunlight
• Obstruction of airflow
• A fault was found internal to
drive
• High line voltage
• Internal voltage too high
• Broken pipe or large leak is
detected in the system
• Drive runs at full power for 10
minutes without reaching
pressure setpoint
• Large water draw, such as a
sprinkler system, does not allow
system to reach pressure
setpoint
• Motor phase currents differ by
20% or more.
• Motor is worn internally
• Motor cable resistance is not
equal
• Incorrect motor type setting
(single- or three-phase)
• Motor output cable is damaged
or exposed to water
• Phase to ground short
• Internal temperature sensor is
malfunctioning

Corrective Action

• Open reading on DC test at start.
• Check drop cable and motor resistance, tighten output
connections, repair or replace as necessary.
• Use dry motor to check drive functions. If drive runs and
exhibits an underload fault, drive is good.
• Amperage exceeded 25 amps on DC test at start or SF
amps during running
• Incorrect output wiring, phase to phase short, phase to
ground short in wiring or motor
• If fault is present after resetting and removing motor
leads, replace drive
• Drive heat sink has exceeded max rated temperature,
needs to drop below 194 °F (90 °C) to restart
• Fan blocked or inoperable, ambient above 122 °F (50 °C),
direct sunlight, air flow blocked
• Replace fan or relocate drive as necessary
• Remove debris from fan intake/exhaust
• Remove and clean optional air screen kit (if installed)
• Contact your Franklin Electric Service Personnel
• Unit may require replacement. Contact your supplier.
• Line voltage high
• Check incoming power connections and correct or tighten
if necessary
• If line voltage is stable and measured below 260 VAC and
problem persists, contact your Franklin Electric Service
Personnel
• Check system for large leak or broken pipe
• If the system contains a sprinkler system or is being used
to fill a pool or cistern, disable the Broken Pipe Detection
• Check resistance of motor cable and motor windings
• Verify motor type matched drive settings (single- or
three-phase)
• Check motor cable insulation resistance with megger
(while not connected to drive). Replace motor cable if
needed.
• Contact your Franklin Electric Service Personnel
• If problem persists, unit may require replacement. Contact
your supplier.