POSSIBLE TROUBLESHOOTING

In the event of problems the boiler stops automatically and runs the shutdown process and the display shows text regar-
ding the motivation of the shutdown (see the various alarms below).
Never pull the plug during shutdown on account of malfunction.
To start the boiler up again after a shutdown, let the shutdown procedure end (10 minutes marked by a beep) tand then
press the button 0/1.
Do not turn the boiler on again before checking the cause of the malfunction and CLEANING/ EMPTYING the crucible.
INDICATION OF POSSIBLE CAUSES OF MALFUNCTION AND INDICATIONS AND REMEDIES:
1) Signalling:
H2O PTC_FAULT
Problem:
Shuts down due to the water temperature sensor being broken or disconnected.
Actions:
- Check connection of the sensor to the control board.
- Verify functionality by means of a cold test
2) Signalling:
Verifi c./extract.: (this trips if the smoke extraction speed sensor detects a fault)
Problem:
Shutdown for smoke extraction speed fault detection
Actions:
• Check smoke extractor function (devolution sensor connection) and board (DEALER).
• Check smoke channel for dirt
• Verify the electrical system and earthing system.
• Check eletronic circuit board (DEALER).
3) Signalling:
Stop/Flame: (this trips if the thermocouple detects a smoke temperature lower than the value set,
which it interprets as the absence of fl ames)
Problem:
Turns off due to drop in smoke temperature
Flame may fail for any of the following reasons:
- lack of pellets
- too many pellets have suffocated the fl ame, check pellet quality (DEALER)
- the maximum thermostat has intervened (rare, this only intervenes in the event of excessive smoke
temperature) (DEALER)
4) Signalling:
Block_FI/NO Start: (intervenes if a fl ame fails to appear within a maximum of 15 minutes,
or if ignition temperature is not reached).
Problem:
Turns off due to incorrect smoke temperature during ignition
Distinguish either of the following cases:
Flame does NOT appear
Actions:
Check: - combustion chamber position and cleanliness;
- arrival of combustion air in the combustion chamber;
- if the heating element is working (DEALER);
- room temperature (if lower than 3°C use a fi relighter) and damp.
- Try to light with a fi relighter (see page 38).
Flames appear, but AF appears on the display after Ar.
Actions:
Check: (only by the Dealer)
- if the thermocouple is working (DEALER);
- start-up temperature setting in the parameters (DEALER).
5) Signalling:
Black Out: (not a defect of the boiler).
Problem:
Turns off due to lack of electricity
Actions:
• Check electricity connection and drops in voltage.
6 ) Signalling: Fault/RC: (intervenes if the thermo coupling has failed or is disconnected).
Problem:
Turns off due to thermo coupling failed or disconnected
Actions:
• Check connection of thermo coupling to board:
• Check function in cold test (DEALER).
7) Signalling: smoke °C/high.: (turns off due to exceeding maximum smoke temperature).
Problem:
Spegnimento per superamento temperatura massima fumi.
Check (only by the Dealer):
• pellet type, anomaly in smoke extraction,
• smoke channel blocked,
• incorrect installation,
• gear motor 'drift'
8 ) Signalling: H2O TEMPALARM
Problem:
Shuts down due to water temperature being higher than 90 °C.
An excessive temperature may occur because of the following:
• system too small: ask the DEALER to activate the ECO function
• blockage: clean the exchanger pipes, the combustion chamber and the smoke outlet.
- 42
-