Fault
Irregular
ALL
83
combustion
(temporary error)
Flow rate reduced
for (presumed) low
ALL
84
pressure on mains
gas
Internal error
ALL
88
(board component
protection)
Unstable
combustion
ALL
89
feedback signal
error
Combustion set
ALL
90
cannot be reached
error
System has reached
maximum air
ALL
92
correction error (at
the minimum flow
rate)
96
Solution
- Check for blockage in
chimney
- Check gas flow rate
- Contact the Technical
Assistance Centre
- Contact the Technical
Assistance Centre
- Contact the Technical
Assistance Centre
- Contact the Technical
Assistance Centre
Type
No.
Fault
Combustion set
ALL
93
cannot be reached
error
Flame signal micro
ALL
95
interruptions error
Block due to
ALL
96
clogging in smoke
outlet
SW error, board
ALL
98
start-up
ALL
99
General board error
Frequent relief
-
-
valve intervention
Limited production
-
-
of domestic hot
water
EN
Solution
- Contact the Technical
Assistance Centre
- Contact the Technical
Assistance Centre
- Check for blockage in
chimney
- Contact the Technical
Assistance Centre
- Contact the Technical
Assistance Centre
- Check circuit pressure
- Check expansion vessel
- Check the diverter valve
- Check that plate heat
exchanger is clean
- Check domestic hot water
circuit valve