BTL6-A/C/E/G500-M _ _ _ _ -PF-S115
Micropulse Transducer in a Flat Profile Housing
4
Installation and connection (continued)
4.4

Electrical connection

Pin
BKS-S115-...
BKS-S116-...
1
Yellow
2
Gray
3
Pink
4
Red
5
Green
6
Blue
7
Brown
8
White
Unassigned leads can be connected to the GND on the controller side but not to the shield.
1)
Reference potential for supply voltage and EMC-GND.
2)
Tab. 4-2:
Pin assignment of S115 connector
4.5

Shielding and cable routing

Defined ground!
The transducer and the control cabinet must be
at the same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect transducer and controller using a shielded
cable.
Shield: Braided copper shield with minimum 85%
coverage.
Shield is internally connected to connector housing.
Magnetic fields
The position measuring system is a magnetostrictive
system.
It is important to maintain adequate distance between the
transducer and strong, external magnetic fields.
Cable routing
Do not route the cable between the transducer, controller,
and power supply near high voltage cables (inductive stray
noise is possible).
Inductive stray noise from AC harmonics (e.g. from phase
angle controls) are especially critical and the cable shield
offers very little protection against this.
Cable length
Cable length max. 20 m. Longer cables may be used if
their construction, shielding and routing prevent noise
interference.
10
english
-A500
-G500
Not used
0 V
Not used
La (programming input)
0 to 10 V
−10 to 10 V
0.1 to 20 mA
GND
10 to 30 V
Lb (programming input)
-C500
-E500
1)
1)
4 to 20 mA
2)
Noise elimination
To avoid equipotential bonding - a current flow - through
the cable shield, please note the following:
Use insulating bushes
Put the control cabinet and the system in which the
BTL6 is located to the same ground potential.
Fig. 4-8:
Pin assignment of S115
connector (view of connector
pins of transducer)