The UPS cabinets use forced air cooling to regulate internal component temperature. By
default, air inlets are in the front of the cabinet and outlets are in the rear, see illustration 5.
Allow clearance in front of and behind each cabinet for proper air circulation. With the
optional top air exhaust kit, it is possible to configure the air outlets in the top rear of the
cabinet. With this option, the UPS can be installed against a wall or back-to-back. Make
sure that the cooling air that enters the UPS does not exceed the specified maximum
ambient temperature. For ventilation requirements, refer to the Eaton 93PM UPS 100-500
kVA User's and Installation Guide.
Table 2. UPS cabinet minimum clearances
From the top of the cabinet
From the front of the cabinet
From the rear of the cabinet
*) 0 mm if top air exhaust kit
installed
From the side of the cabinet
Table 3. Minimum recommended multi-core cable and fuse sizes for rectifier and bypass input and
UPS output cables
UPS model
93PM-100(400)
93PM-150(400)
93PM-200(400)
93PM-250(400)
93PM-300(400)
93PM-350(400)
93PM-400(400)
93PM-100(500)
93PM-150(500)
93PM-200(500)
93PM-250(500)
93PM-300(500)
500 mm
900 mm
450 mm*
0 mm
Rectifier, static
bypass and
Phase cables
maintenance
bypass input
fuse [A]
95 mm
2
185 mm
2
240 mm
2
2 x 120 mm
2
per
phase
2 x 185 mm
2
per
phase
2 x 240 mm
2
per
phase
2 x 240 mm
2
per
phase
95 mm
2
185 mm
2
240 mm
2
2 x 120 mm
2
per
phase
2 x 120 mm
2
per
phase
PE cable [mm
200
50
315
95
400
120
500
120
630
185
700
240
800
240
200
50
315
95
400
120
500
120
500
120