UPS model
93PM-350(500)
93PM-400(500)
93PM-450(500)
93PM-500(500)
Make sure that prospective short-circuit current resulting at the UPS input terminals is
equal or less than conditional short-circuit current declared on the type plate of the UPS.
Table 4. Minimum recommended cable and fuse sizes for external battery bank
UPS model
93PM-100(400)
93PM-150(400)
93PM-200(400)
93PM-250(400)
93PM-300(400)
93PM-350(400)
93PM-400(400)
93PM-100(500)
93PM-150(500)
93PM-200(500)
93PM-250(500)
93PM-300(500)
93PM-350(500)
93PM-400(500)
93PM-450(500)
93PM-500(500)
Refer to national and local electrical codes for acceptable external wiring practices.
For information on rated and maximum currents for rated power and voltage, refer to the
Eaton 93PM UPS 100-500 kVA User's and Installation Guide.
For the battery terminals in the 93PM with a separate battery option, refer to the Eaton
93PM UPS 100-500 kVA User's and Installation Guide.
6 6
Phase cables
2 x 185 mm
2
per
phase
2 x 240 mm
2
per
phase
2 x 240 mm
2
per
phase
)
2 x 240 mm
2
per
phase
CAUTION
Battery cable, pos. &
Battery fuse [A]
neg. line
185 mm
2
per pole
240 mm
2
per pole
2 x 185 mm
2
per pole
2 x 240 mm
2
per pole
2 x 240 mm
2
per pole
4 x 120 mm
2
per pole
4 x 185 mm
2
per pole
120 mm
2
per pole
240 mm
2
per pole
2 x 120 mm
2
per pole
2 x 185 mm
2
per pole
2 x 240 mm
2
per pole
4 x 120 mm
2
per pole
4 x 120 mm
2
per pole
4 x 185 mm
2
per pole
4 x 185 mm
2
per pole
Rectifier, static
bypass and
maintenance
PE cable [mm
bypass input
fuse [A]
630
800
800
800
315
400
630
700
800
1000
1250
250
400
500
630
800
1000
1000
1250
1250
]
2
185
240
240
240