Paramete
rs
C00728/3 nMainSetValue_
C00727/3 bSetSpeedCcw
C00727/4 bJogSpeed1
11. If required, adapt further parameters.
12. Save parameter settings with function key
the memory module.
6.3.4
SET mode
In SET mode, the inverter is controlled via the diagnosis terminal. You can change
the speed setpoint and enable or inhibit the inverter (RFR/run). Other setpoint
sources are ignored.
Activate SET mode: press "DISP" softkey button and confirm with "OK"
ƒ
softkey button.
Exit SET mode: press "DISP" softkey button and confirm with "OK" softkey
ƒ
button.
)
Note!
SET mode can only be activated in the "OperationEnabled" device
state (controller inhibit is deactivated, green LED on the inverter is lit
permanently).
ƒ
EDK84DGDVBxxx4 DE/EN/FR/ES/IT 8.3
Commissioning via the diagnosis terminal
Name
Info
Main setpoint for the application 100 % º
a
reference speed (C00011)
Change of direction of rotation
"0": CW rotation
"1": CCW rotation
Selection of fixed setpoint 1
"0": Main setpoint (C00728/3) active.
"1": Fixed setpoint 1 (C00039/1) active.
Controller inhibit is only indicated in the keypad. The cause of
controller inhibit is shown in detail in C00158 (¶ 8400 motec
reference manual).
l
Commissioning
SET mode
Lenze setting
safe against mains failure in
6
0.00 %
0
0
101