Informazioni sulla sicurezza

Informazioni sulla sicurezza per l'installazione secondo UL/CSA

2.2
Informazioni sulla sicurezza per l'installazione secondo UL/CSA
Originale − Inglese
J
Warnings!
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
...
218
Use Class 1 wire only.
Intended for use with 75 °C wire.
Intended for use with copper conductors only.
Suitable for use in a surrounding air temperature of 45 °C, and
– additionally 55 °C when de−rating rules are followed.
Hot surface. Risk of burn.
Should this device be mounted on a motor, the combination
needs to be suitable for the type rating.
The supply terminals are to be tightened to:
– For model suffix's 371, 551, 751, 112, 152 tighten to
4.4 − 5.3 lb−in.
– For model suffix's 222, and 302, tighten to 7 lb−in.
These devices are suitable for use on a circuit capable of
delivering not more than 200 000 rms Symmetrical Amperes,
480 V maximum
– When protected by CC, R, T, or J class fuses or
– When protected by a circuit breaker having an interrupting
rating not less than 200 000 rms symmetrical amperes, 480 V
maximum.
These devices are suitable for motor group installation on a
circuit capable of delivering not more than 200 000 rms
Symmetrical Amperes, 480 V maximum
– When protected by CC, R, T, or J class fuses or
– When protected by a circuit breaker having an interrupting
rating not less than 200 000 rms symmetrical amperes, 480 V
maximum.
Use fuses and circuit breakers only.
l
EDK84DGDVBxxx4 DE/EN/FR/ES/IT 8.3