6
Commissioning
Commissioning steps
}
Danger!
Great hazard potential during commissioning
Incorrect settings may cause unexpected and dangerous motor and
system movements.
Possible consequences:
ƒ
ƒ
Protective measures:
ƒ
ƒ
6.2
Commissioning steps
Proceed step by step:
Switch on the mains
ƒ
Monitor status display
ƒ
–
After a short initialisation time, the display must be blinking green.
Deactivate requirements of the safety function
ƒ
Set controller enable
ƒ
–
After the set starting time, the motor must rotate with the speed set.
Initial check of the expected behaviour:
ƒ
–
Direction of rotation?
–
Starting time?
–
Speed?
–
Speed control?
Check of optional control functions:
ƒ
–
Is the analog setpoint selection working?
–
Are the digital control signals, e.g. limit switches, working?
–
Is the connected motor holding brake working?
–
Is the function for changing over the rotating direction working?
–
Is the requirement with regard to the safety function working?
–
Are the control signals via fieldbus working?
Switch off drive
ƒ
–
Reduce speed
–
Inhibit controller enable
–
Switch off mains
92
Damage to material assets
Injury to persons
Clear hazardous area
Observe safety instructions and safety clearances
l