No. of Fault and Action
Flashes
7
Over Temperature
Action: Fault clears and
controller restarts when
its internal temperature
drops back down to
acceptable level.
8
Open lead
Action: Controller shuts
off and stays off. Fault
can only be cleared by
turning power off for
1 minute. If cause of fault
persists then fault will
re-occur.
9/Solid Controller Fault
Red
Action: Fault never clears
even if power is cycled.
Off
Low Voltage
Action: This fault clears
as soon as voltage returns
to normal level.
This warranty applies to the Balanced Flow Series Controller manufactured by Goulds Pumps.
Any part or parts found to be defective within the warranty period shall be replaced at no charge to the dealer during the warranty period. The warranty period shall
exist for a period of twelve (12) months from date of installation or eighteen (18) months from date of manufacture, whichever period is shorter.
A dealer who believes that a warranty claim exists must contact the authorized Goulds Pumps distributor from whom the equipment was purchased and furnish
complete details regarding the claim. The distributor is authorized to adjust any warranty claims utilizing the Goulds Pumps Customer Service Department.
The warranty excludes:
(a) Labor, transportation and related costs incurred by the dealer;
(b) Reinstallation costs of repaired equipment;
(c) Reinstallation costs of replacement equipment;
(d) Consequential damages of any kind; and,
(e) Reimbursement for loss caused by interruption of service.
For purposes of this warranty, the following terms have these definitions:
(1) "Distributor" means any individual, partnership, corporation, association, or other legal relationship that stands between Goulds Pumps and the dealer in
purchases, consignments or contracts for sale of the subject equipment.
(2) "Dealer" means any individual, partnership, corporation, association, or other legal relationship which engages in the business of selling or leasing equipment
to customers.
(3) "Customer" means any entity who buys or leases the subject equipment from a dealer. The "customer" may mean an individual, partnership, corporation, limited
liability company, association or other legal entity which may engage in any type of business.
Goulds Pumps, Balanced Flow and the ITT Engineered Blocks symbol are
registered trademarks and tradenames of ITT Industries.
©2003 Goulds Pumps
Printed in U.S.A.
8
Cause and Reaction
If temperature of the controller reaches 158°F (70°C), pump will turn off. Pump will
restart automatically when controller cools off. Check for fan failure. Fan should turn
on when cabinet temperature is around 130-140°F. If it doesn't, check fan
connections or replace as needed. Ensure that the external fan intake filter is not
blocked or clogged. It can be removed for cleaning and replacement is available.
Verify motor is connected to BF15 controller with no breaks in the wire.
Replace Controller
Check power input. Power input must be at least 196VAC. If OK Replace controller.
Table 3: Fault Blink Codes