10 EN – USA quick installation guide
(3BFE64059629 [English]), available on the Internet at
www.abb.com/drives/documents.
Select the power cables
Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.
Typical power cable sizes are listed in table
sizing, see the hardware manual.
Ensure the cooling
DA
See table
A
on page
allowed operating temperature range of the drive without derating is -15 to +40 °C.
USA

Protect the drive and input power cable

DA
See table
A
on page
DE
NEC. Check that the operating time of the fuse is below 0.5 seconds for frame R6
and below 0.1 seconds for frames R7 to R9. Obey local regulations.
ES
Install the drive on the wall
FI
See figure
A
on page 101. For UL Type 12 drives: Install also the hood to the drive.
FR
Check the compatibility with IT (ungrounded), corner-
IT
grounded delta, midpoint-grounded delta and TT systems
NL
The standard drive with ground-to-phase varistors connected can be installed to a
symmetrically grounded TN-S system. For other systems, see the hardware manual
PT
and ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor
disconnecting instructions (3AUA0000125152 [English]).
RU
SV
TR
CN
105
for the losses and the cooling air flow through the drive. The
105
for the UL class T fuses for branch circuit protection per
B
on page 102. For the conditions of the