12 EN – USA quick installation guide
please consult the manufacturer's instructions. Note: Moisture inside the motor
casing will reduce the insulation resistance. If moisture is suspected, dry the motor
and repeat the measurement.

Connect the power cables

See figures B,
the motor cabling.
1. Remove the front cover. UL Type 1 drives: Release the retaining clip with a
screwdriver (a) and lift the cover from the bottom outwards (b).
2. UL Type 1 drives: Remove the cable entry box cover by undoing the mounting
DA
screws.
USA
3. Attach the residual voltage warning sticker in the local language next to the
control board top.
DA
4. Remove the side plates of the cable entry box.
DE
5. Remove the shroud on the power cable terminals by releasing the clips on the
sides with a screwdriver and lifting (a). If parallel cables are installed, knock out
ES
holes for the cables (b).
6. Knock out the shrouds on the power cable terminals for the cables to be installed.
FI
7. Fasten the cable conduits to the cable lead-through plate holes. Strip the cable
FR
ends. Slide the cables through the connectors.
8. Connect the twisted cable shields to the grounding terminals.
IT
9. Connect the conductors of the input and motor cables. Tighten the screws.
NL
10. Units with option +D150: Connect the conductors of the brake resistor cable to the
R+ and R- terminals.
PT
11. Reinstall the shroud on the power terminals.
RU
12. Reinstall the side plates of the cable entry box.
SV
13. Secure the cables outside the unit mechanically.
TR
Connect the control cables
Install the control cable grounding shelf in the cable entry box (see figure
CN
106).
See figure
G
on page 106.
C
and
E
on pages
105
and 106. Use symmetrical shielded cable for