4 EN – Quick installation guide
(3BFE64059629 [English]), available on the Internet at
www.abb.com/drives/documents.
Select the power cables
Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.
Typical power cable sizes are listed in table
sizing, see the hardware manual.
Ensure the cooling
EN
See table
B
on page
allowed operating temperature range of the drive without derating is -15 to +40 °C.
DA
Protect the drive and input power cables
DE
See table
B
on page 102.
ES
Install the drive on the wall
FI
See figure
A
on page 101.
FR
Check the compatibility with IT (ungrounded), corner-
IT
grounded delta, midpoint-grounded delta and TT systems
NL
The standard drive with ground-to-phase varistors connected can be installed to a
symmetrically grounded TN-S system. For other systems, see the hardware manual
PT
and ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor
disconnecting instructions (3AUA0000125152 [English]).
RU
SV
TR
CN
102
for the losses and the cooling air flow through the drive. The
B
on page 102. For the conditions of the