INSTALLATION
11.5
Electrical characteristics
1
2
A
Fig. 11.4
Electrical layout for outdoor and indoor connection.
Legend
1
Connector strip for the outdoor unit
2
Connector strip for the indoor unit
A + B =
VAM 3-050 W2N / VAM 3-060 W2N
A + B + C =
VAM 3-085 W3N
A + B + C + D = VAM 3-085 W4N
Power supply (V/Ph/Hz)
Supply section up to 25 meter (in mm 2 )
Indoor / Outdoor
Thermal-magnetic circuit breaker, type D (A)
Interconnection section up to 25 meter (mm 2 )
Inteconnect shielded cable or not (YES/NO)
Immediatte residual current protector (A)
Table 11.1 Electrical Characteristics
- 18 -
B
VAM 3-050 W2N
220-240V / 1 / 50
2.5
Outdoor
16
2.5
NO
0.03
C
VAM 3-060 W2N
VAM 3-085 W3N
220-240V / 1 / 50
220-240V / 1 / 50
2.5
Outdoor
Outdoor
16
2.5
NO
0.03
D
VAM 3-085 W4N
220-240V / 1 / 50
6
6
Outdoor
25
25
2.5
2.5
NO
NO
0.03
0.03
VAI3-MWN-I_EN - 09/14 - Vaillant