Li-Ion Batteries; Configuring The Inverter To Work Only With The Pv Array, Without Batteries; Configuring The Operation Mode And Its Settings - Ingeteam INGECON SUN STORAGE 1Play TL M Manual De Instalacion Y Uso

Ocultar thumbs Ver también para INGECON SUN STORAGE 1Play TL M:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Ingeteam
CAUTION
An incorrect configuration of these settings can reduce the battery life. Ingeteam accepts no liability for the
consequences that may arise from incorrect configuration of the unit by the user and/or the installer.
Setting
Nominal Voltage
Minimum Voltage
Time for Minimum voltage
Capacity (C20h)
Capacity (C5h)
Maximum Charge Current
Maximum Discharge Current
Absorption voltage
Flotation voltage
Equalization voltage
Duration of Equalization charge

Li-Ion batteries

The Li-Ion batteries suitable for the INGECON SUN STORAGE 1Play have their own advanced battery
management, which is usually programmed by the manufacturer and integrated in the batteries (BMS). Ingeteam
cannot in any way change the operation of this external advanced battery management.
INFO
For more information about the compatible Li-Ion batteries, see the "List of Li-Ion batteries approved for the
INGECON SUN STORAGE 1Play TL M" available on the Ingeteam website.
If the battery model is not in the list, contact Ingeteam.
18.7.2. Configuring the inverter to work only with the PV array, without
batteries
These inverters can work only from the PV array, without using the battery input. To do this:
1.
Go to Configuration > Advanced Settings > Type of Battery.
2.
Select as No Configuration.
In this operating mode, if the grid is available, the inverter remains connected even with low PV power. This allows
to have the unit connected and monitor the installation at all times.
To disable this function, access Configuration > Advanced Settings > Other Settings > Low PV Power Stop.

18.7.3. Configuring the operation mode and its settings

These inverters can be used both in stand-alone installations and installations connected to grid.
INFO
For more information about this type of installation, see the "Technical guide for installations with
INGECON SUN STORAGE 1Play TL M" available on the Ingeteam website.
48
Rated voltage of the battery bank (V).
Minimum voltage of the battery bank to avoid complete discharges, even stopping the supply
from the batteries to the consumers (V).
Duration of the minimum voltage of the battery bank. Time for which the battery bank must be
maintained at the minimum voltage to avoid complete discharges (seconds).
C20 capacity specified by the battery manufacturer (Ah). This setting is used to precisely
determine the battery state of charge (SOC).
C5 capacity specified by the battery manufacturer (Ah). This setting is used to precisely
determine the battery state of charge (SOC).
Maximum charge current of the battery bank (A).
Maximum discharge current of the battery bank (A).
Absorption voltage of the battery bank (V). Allows to charge the batteries at constant voltage.
Flotation voltage of the battery bank (V). Allows to charge the batteries completely.
Equalization voltage of the battery bank (V). This parameter is used when maintenance has to
be performed on the liquid electrolyte batteries. Consult the battery manufacturer about this
parameter (see
"18.13. Performing an equalization charge of the
Duration of equalization charge. Time for which the battery bank must be maintained at the
equalization voltage (minutes).
Description
batteries").
ABH2014IQM01_A- Installation and Operation Manual
Using the unit

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido