Ingeteam
INFO
The ventilation test only checks the turning of the fans. A positive ventilation test alone does not indicate that
the system's ventilation status is correct. To assure proper performance of the ventilation system, also check
that there are no elements obstructing air passage and that the fans are properly installed.
18.15. Li-Ion battery calibration
CAUTION
An incorrect configuration of these settings can reduce the battery life. Ingeteam accepts no liability for the
consequences that may arise from incorrect configuration of the unit by the user and/or the installer.
For Li-Ion batteries the manufacturer recommends running a periodic battery calibration (check with
manufacturer).
The purpose is to equalize the state of charge (SOC) of all the cells, preventing a premature failure of individual
cells, and extending the service life of the battery.
This process consists of two steps:
1.
Full battery charge process. The battery status will display Calibration - Charging .
2.
Battery discharge process. The battery status will display Calibration - Discharging.
During the calibration process, the parameters configured in section
and its settings"
do not apply. In addition, although it is not permitted to charge the batteries from the grid (see
"18.7.6. Configuring the battery charge from the distribution
charge the batteries with at least 400 W from the distribution grid.
The calibration process will end automatically when the BMS determines that all the cells have the same state of
charge (SOC).
The calibration process is activated by default. If you wish to disable the battery calibration, go to Configuration >
Advanced Settings > Other Settings > Lithium-ion Battery Calibration Process.
58
"18.7.3. Configuring the operation mode
grid"), if required by the calibration, the inverter will
ABH2014IQM01_A- Installation and Operation Manual
Using the unit