Electrical Connections; Table Of Parameters To Be Established In The Kl1 Control Unit, Dedicated To Ebara Technicians - EBARA 2SP EFC 1,5T-1 Instrucciones Para La Instalación Y El Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

8.7 ELECTRICAL CONNECTIONS

8.7.1 Before connecting the power cables to terminals L1 - L2 - L3 on the insulating switch, ensure that the main switch
on the power distribution panel is in OFF position (O), and that no one can switch on the power accidentally.
8.7.2 Scrupulously observe all the regulations in force concerning safety and accident prevention.
8.7.3
Ensure that all the terminals are fully tightened, paying particular attention to the earth terminal.
8.7.4 Connect the cables to the terminal board as indicated in the wiring diagrams given in the enclosed booklet.
8.7.5 Check that all the connecting cables are in excellent condition, with the external sheathing unbroken.
8.7.6
ATTENTION ! In the system, install differential switches type:
Class A, with adjustable dispersion current: 300 mA, selective, protected
against sudden tripping, delay time 0.5 seconds.
Provide automatic protection of the supply line against short circuits by means of ACR fuses type
_gG" according to the following table:
8.7.7
The apparatus must be correctly and safely earthed as required by the
regulations in force.
8.7.8 Depending on the type of installation, limit the maximum length of the power .
8.7.9 Instrumental checks to be carried out by the installer:
a) continuity of the protection leads and of the main and supplementary equipotential circuits;
b) insulation resistance of the electric system;
c) test efficiency of the differential protection;
d) test the applied voltage;
e) test operation.
9. TABLE OF PARAMETERS TO BE ESTABLISHED IN THE KL1 CONTROL UNIT, DEDICATED TO EBARA
TECHNICIANS
Parameter
Enter key
Language
Languages in which the parameters are written (Italian,
1: ENGLISH
English, French, German, Spanish).
Italian, English, French, German, Spanish* .
0
Type of system
1 Inverter fixed on pump.
1 : Inverter fix
2 One inverter exchanged on all the pumps.
2 : exchange inv.
3 Serial comntrol multiinverter
3 : Exc. Mul.inv
4 Circulatin system Control
4 : Heating pumps
RS485 address
Data to be set for multi-inverter panels with serial
communication.
Type of sensor
1
Relative pressure transmitter.
1: RELAT PRES.
2
Differential pressure transmitter or use second
2: DIFFER. PRESS.
pressure sensor Input.
Reg, type
1 negative feedback = for submerged pump pressurisation
1:negative
systems
2: positive.
2 positive feedback = for refrigeration systems
Type of control
1 : Analogue.
1 : ANALOGUE
2 : Serial.
2: SERIAL
Number of Pumps
Selection of number of system pumps. Extendable to up to
0:-:3
eight pumps.
Sensor Press.
Full scale pressure of Pressure Transmitter.
00,0 (bar)
Flow resistance
Flow resistance compensation for sequential pump start-
0,0 (bar)
up.
Nominal Pump
Nominal pressure of pump at 0 litres.
press.
00,0 (bar)
Reference P.
System pressure to be kept constant.
00,0 (bar)
Proportional lim.
Pressure range within which the control unit does not
0,0 (bar)
correct the pressure.
Restart pressure
Pressure at which the inverter starts up again.
Description
Enter key
1
2
3
4
Control unit address = 00
ENGLISH
Range
0 -:- 99999
0 -:- 4
1 -:- 4
00
1 -:- 2
1 -:- 2
1 -:- 2
1-:-4
(8)
00-:-99
0,0 -:- 1,0
0,00 -:- 25,5
0,00 -:- 25,5
0.0 -:- 9.9
0.0 -:- 9.9
29
SetUP
Meas. unit
Service
/
31100
English
/
2
00
1
1
1
1-:-4
bar
10
bar
0,0
bar
8,00
bar
6,00
bar
0,2
bar
0,3

Publicidad

Tabla de contenido
loading

Tabla de contenido