Installation; Technical Data - EBARA 2SP EFC 1,5T-1 Instrucciones Para La Instalación Y El Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

7. INSTALLATION

Carefully observe the power supply values specified on the rating plate.
The electrical panel is supplied pre-assembled and wired to the pumpset. The electrical panel must be
installed on a dry surface, in an atmosphere that is free from oxidizing or corrosive gases, and where no
vibrations occur. If installed outdoor, the units must be fully protected from direct sunlight. Make sure
that the ambient temperature is kept within the operating limits specified below . High temperatures lead
to rapid ageing of all the components, causing more or less severe malfunctions.
It is also advisable for the person who installs the panels to ensure that the cable clamps are watertight.
Use the cable clamp gripping rings provided to block the cables (power supply to the panel) and the cables
of any external controls connected by the installer), so as to prevent the cable clamps from working loose.

8. TECHNICAL DATA

Rated input voltage :
Phases :
Frequency :
Number of pumps that can be
connected :
Panel models:
Max. rated output power (kW):
Max. rated using current (A):
Panel model:
Max. rated output power (kW):
Max. rated using current (A):
Field of use environment temperature: -10°C + 40°C
Storage environment temp. limit:
Relative humidity (without
condensation):
Max. altitude:
Degree of protection:
Panel construction:
ENGLISH
400 V +/- 10%
3
50-60 Hz
Two, for models:
2SP EFC 1,5T-1 - 2SP EFC 2,2T-1 - 2SP EFC 3T-1 - 2SP EFC 4T-1 -
2SP EFC 5,5T-1 - 2SP EFC 7,5T-1 - 2SP EFC 11SD-1 - 2SP EFC 15SD-1 -
2SP EFC 18,5SD-1 - 2SP EFC 22SD-1 - 2SP EFC 30SD-1.
Three, for models:
3SP EFC 1,5T-1 - 3SP EFC 2,2T-1 - 3SP EFC 3T-1 - 3SP EFC 4T-1 -
3SP EFC 5,5T-1 - 3SP EFC 7,5T-1 - 3SP EFC 11SD-1 - 3SP EFC 15SD-1 -
3SP EFC 18,5SD-1 - 3SP EFC 22SD-1 - 3SP EFC 30SD-1.
Four, for models:
4SP EFC 1,5T-1 - 4SP EFC 2,2T-1 - 4SP EFC 3T-1 - 4SP EFC 4T-1 -
4SP EFC 5,5T-1 - 4SP EFC 7,5T-1 - 4SP EFC 11SD-1 - 4SP EFC 15SD-1 -
4SP EFC 18,5SD-1 - 4SP EFC 22SD-1 - 4SP EFC 30SD-1.
2SP EFC 1,5T-1
2SP EFC 2,2T-1
3SP EFC 1,5T-1
3SP EFC 2,2T-1
4SP EFC 1,5T-1
4SP EFC 2,2T-1
2x1,5
2x2,2
3x1,5
3x2,2
4x1,5
4x2,2
2x3,7
2x5,3
3x3,7
3x5,3
4x3,7
4x5,3
2SP EFC 11SD-1
2SP EFC 15SD-1
3SP EFC 11SD-1
3SP EFC 15SD-1
4SP EFC 11SD-1
4SP EFC 15SD-1
2x11
2x15
3x11
3x15
4x11
4x15
2x23
2x31
3x23
3x31
4x23
4x31
-25°C +55°C
40% at 50°C MAX (90% at 20°C ).
1000 m (a.s.l.)
IP55, for models with inverter power up to 3 kW
IP 54, for models with inverter power from: 4, 5.5 and 7,5 kW.
IP44, for models with inverter power from: 11 kW and higher powers.
In accordance with EN 60204-1, EN 60439-1, EMC standards applied:
EN50081-1 EN50082-2 for civil use and for light industry.
22
2SP EFC 3T-1
2SP EFC 4T-1
3SP EFC 3T-1
3SP EFC 4T-1
4SP EFC 3T-1
4SP EFC 4T-1
2x3
2x4
3x3
3x4
4x3
4x4
2x7,2
2x9
3x7,2
3x9
4x7,2
4x9
2SP EFC 18,5SD-1
2SP EFC 22SD-1
3SPEFC-18,5SD-1
3SP EFC 22SD-1
4SPEFC-18,5SD-1
4SP EFC 22SD-1
2x18,5
2x22
3x18,5
3x22
4x18,5
4x22
2x37
2x43
3x37
3x43
4x37
4x43
2SP EFC 5,5T-1
2SP EFC 7,5T-1
3SP EFC 5,5T-1
3SP EFC 7,5T-1
4SP EFC 5,5T-1
4SP EFC 7,5T-1
2x5,5
2x7,5
3x5,5
3x7,5
4x5,5
4x7,5
2x12
2x15,5
3x12
3x15,5
4x12
4x15,5
2SP EFC 30SD-1
3SP EFc 30SD-1
43SP EFC 30SD-1
2x30
3x30
4x30
2x61
3x61
4x61

Publicidad

Tabla de contenido
loading

Tabla de contenido