0,0 (bar)
Correction KP
Proportional correction of error between the system pressure
100
and the Reference Pressure.
Correction KI
Correction in time of error between the system pressure and
100
the Reference Pressure.
Acceleration
Inverter start-up time from Min speed to Max speed.
001 (sec)
Deceleration
Inverter stop time from Max speed to Min speed.
001 (sec)
Min. spd Per red %
Inverter's minimum speed level setting for stop inverter
85
pumps control .
Min. speed %
Inverter's minimum speed level setting for stop cascade
60
pumps control .
Periodic reduction
Reduction of reference pressure to stop the pump with the
0,00 (bar)
inverter.
Per. Red. Interv.
Delay in reduction of reference pressure to stop the pump with
00 (sec)
the inverter.
Pump stop delay 000
Stop delay of the pumps following the first inverter supply.
(sec)
P. startup delay
Delay in start-up of pumps following the first one
00 (sec)
Danger Press.
Pressure setting at which the control unit goes into
00,0 (bar)
overpressure alarm mode.
Delay in signal
Delay the signal of sensor. If it is 00 then minimal delay. If it
00 (%)
is 100 then maximum delay.
Min.Press. AllH2O
Pressure value to be set based on the pressure in the delivery
0.0 (BAR)
circuit. The factory setting is 0.5 bar.
Pump rot. Interr.
Time of daily changeover of the starting order of the pumps,
00
with the following settings:
0 = no changeover.
1 to 24 changeover based on set hour.
25= changeover at each new start-up.
Flow unit meas. 0 :
Selection of unit of measurement for the flow meter L/sec,
(UnitMeas.)
L/min, M3h, G/s, G/m.
F.s.flow sensor
Selection of flow meter full scale.
0000
Calibr. factor TA
Coefficient for calibration of amperometric
00,0
0
transformer.
Calibr. factor TV
Coefficient for calibration of voltmetric transformer.
00,0
0
Min.press.H2O
Pressure value to be set based on the pressure in the delivery
0,0 (BAR)
circuit. The factory setting is 0.5 bar.
P1, P2, P3, P4
Pump maintenance time,
maint time
P1,P2, P3, P4 maint. step-in
00000
P1, P2, P3, P4
P1 pump operating hours
oper. Hours
00000
The boldface parameters must be calibrated during the system startup phase.
* = Spanish language is not in the control unit (supplied on request).
ENGLISH
0 -:- 250
0 -:- 250
0 -:- 200
0 -:- 200
0.00 -:-
100%
0.00 -:-
100%
0.00-:-5
0 -:- 99
0 -:- 99
0 -:- 99
0 -:- 100
0 -:- 100
0,00 -:- 25,5
0 -:- 25
0 -:- 4
0 -:- 9999
0 -:- 99
0 -:- 99
0,00 -:- 1
0 -:- 99999
0 -:- 99999
30
/
50
/
50
sec.
1
sec.
1
%Vmax
90
%Vmax
76
bar
0,5
sec.
30
sec.
2
sec.
2
%
80
%
00
bar
0,5
hours
25
/
0: L/sec
/
0000
N°
00,0
N°
00,0
bar
0,5
hours
10000
hours
00000