6. Troubleshooting

If the UPS system does not operate correctly, please first identify the problem using the table below.
Symptom
No indication and alarm in the front
display panel, even though the mains is
normal.
The
icon and the warning code
on LCD screen and alarm beeps every
second.
The
and
icons flash on LCD and
alarm beeps every second.
The
and
icons flash on LCD and
alarm beeps twice every second.
Fault code 43 is shown, the
on LCD and alarm beeps continuously.
Fault code 14 is shown, the
icon lights on LCD and alarm beeps
continuously.
Other fault codes are shown on LCD and
alarm beeps continuously.
Battery backup time is shorter than
nominal value.
The
and
icons flash on LCD and
alarm beeps every second.
Warning code 02 is shown, the icon
flashes on LCD and alarm beeps every
second.
Possible cause
AC input wiring is not connected properly.
EPO function is activated. At this time,
flash
the EPO switch is in "OFF" status or the
jumper is open.
Internal or external batteries are
connected improperly.
UPS is overloaded.
UPS is overloaded. Devices connected to
the UPS are fed directly by the electrical
network via the Bypass.
After repeated overloads, the UPS is
locked in the Bypass mode. Connected
devices are fed directly by the mains.
UPS is overloaded and results in a fault.
icon lights
The UPS will then shut down automatically.
The UPS shuts down automatically
because short circuit occurs on the UPS
output.
An internal UPS fault has occurred.
Batteries are not fully charged.
Batteries are defective.
Fan is locked or not working, or the UPS
temperature is too high.
The input neutral wire is disconnected.
The L2 or L3 input fuse is damaged.
Remedy
Check that all input wiring is firmly connected
to AC mains.
Set the circuit in the closed position to
disable the EPO function.
Check that batteries are connected properly.
Remove excess loads from UPS output.
Remove excess loads from UPS output.
Remove excess loads from UPS output first.
Then shut down the UPS and restart it.
Remove excess loads from UPS output and
restart it.
Check output wiring and if connected devices
are in short circuit status.
Contact Tripp Lite Tech Support.
Charge the batteries for at least 10 hours
and then check capacity. If the problem still
persists, contact Tripp Lite Tech Support.
Contact your Tripp Lite reseller to replace the
battery.
Check fans and contact Tripp Lite Tech
Support.
Check and correct the input neutral
connection. If the connection is ok and the
alarm is still sounding, please refer to the LCD
Settings in section 4.7. To enter the neutral
loss check menu to see if Parameter 3 is
"CHE", press the "Enter" button to make the
"CHE" flash. Then press the "Enter" button to
make the UPS clear the alarm. If the warning
still exists, check L2 and L3 input fuses.
Replace the fuse.
28