Descargar Imprimir esta página

Complete Installation; Troubleshooting Guide - Eaton Crouse-Hinds Serie Información De Instalación Y Mantenimiento

Kit de batería y tablero del cargador de reemplazo elpsm2 k50

Publicidad

Idiomas disponibles

Idiomas disponibles

COMPLETE INSTALLATION

1.
Test emergency lighting system for proper operation (see Table 1 for detail
indication logic).
a)
Turn on the AC power and observe:
Indicating light marked ON should be operating.
Momentarily press the push-to-test button and observe – emergency
lights should be operating.
NOTE: If emergency lights do not operate initially, allow battery to charge for at least
15 minutes or more, then repeat the test procedure. Allow 15 hours charge time
before depending on battery to operate at full capacity.
PILOT LIGHT LAMP REPLACEMENT
1.
Turn OFF supply power to the ELPSM2 Light-Pak and turn OFF the battery
disconnect switch [S794 or S854] located next to the push-to-test button.
2.
Unscrew jewel assembly from pilot light.
3.
Push lamp in, twist counterclockwise, then remove lamp and discard.
4.
Install replacement pilot light lamp.
Pilot light: MB444WCU2-2VF/NR-DP, 2V LED with miniature bayonet
base*
5.
Replace jewel assembly, securely tightening it onto barrel.
6.
Turn "ON" designated disconnect switch.
*Available from Starled, Inc. (www.starled.com)
MAINTENANCE
To avoid explosion, always disconnect primary power source using designated
disconnect switch before opening enclosure for inspection or service.
1.
Conduct periodic testing in accordance with local authority and periodic testing
section of these instructions.
2.
Clean luminaire lens and exterior surfaces periodically. We recommend every
three (3) months or more frequently, if appropriate.
3.
Frequent interior inspection should be made. A schedule for maintenance
check should be determined by the environment and frequency of use. It is
recommended that it should be at least once a year.
4.
Perform visual, electrical and mechanical checks on all components on a regular
basis.
Visually check for undue heating evidenced by discoloration of wires or other
components, damage or worn parts or leakage evidenced by water or corrosion
in the interior.
Electrically check to make sure that all connections are clean and tight.
Mechanically check that all parts are properly assembled.
5.
Do not attempt field replacement or repair of ELPSM20 power supply cover
gasket.
To avoid explosion, clean both flat joint surfaces of body and cover before
closing. Dirt or foreign material must not accumulate on flat joint surfaces.
Surfaces must seat fully against each other to provide a proper explosionproof
seal.
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In
accordance with Eaton's Crouse-Hinds Division's "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended
use and assumes all risk and liability whatsoever in connection therewith.
! WARNING
! CAUTION
MANUAL TESTING
10 second "installation" test – press and release the test button once during
fast charge (blinking status light) to initiate a 10 second quick test. The charger
will switch to emergency mode for 10 seconds, allowing the installer to verify
proper installation of the unit.
30 second test – press and release the test button once during float charge
(steady on). During this test, the lamps will turn on for 30 seconds.
90 minute test – press and release the test button a second time during the
30 second test to change to a 90 minute test. During this test, the circuit will
perform a full battery capacity, charge circuit and LED test.
Canceling test – press and release the test button during the 90 minute test to
return the equipment to its original state (fast charge or float charge).

TROUBLESHOOTING GUIDE

Symptom
LED does not light
LED is blinking twice
LED is blinking three times
LED is blinking four times
Eaton's Crouse-Hinds Division
1201 Wolf Street, Syracuse, New York 13208 • U.S.A.
Copyright
2019
©
Solution
Verify power to equipment
Verify battery is properly connected to
circuit board
Verify battery voltage under no load is 13V
or higher after 15 hour charge. If less than
13V, consult factory for battery replacement.
If replacing the battery does not satisfy the
blink code error, consult factory for circuit
board replacement.
Check lamp connections
Table 2
IF 1873
Revision 1
New 03/19

Publicidad

loading

Este manual también es adecuado para:

Elpsm2 light-pak