Cabling examples

ACSM1-04xx-02A5...016A-4
3
ACSM1-04xx-024A...090A-4
1
4
3
2
Cable clamp on bare shield.
1
PE/Ground connection.
2
Between cable clamp and terminals, cover bare
1
3
shield with insulating tape.
Screw lug detail:
4
2

Wire sizes accepted by power terminals

Drive type ACSM1-04xx...
-02A5...07A0-4
-09A5...016A-4
-024A...090A-4

Tightening torques

Drive type
ACSM1-04xx...
-02A5...07A0-4
-09A5...016A-4
-024A...090A-4
Drive type
ACSM1-04xx...
-02A5...07A0-4
-09A5...016A-4
-024A...090A-4
Quick installation guide - ACSM1-04
Wire size
0.25 ... 4 mm
0.5 ... 6 mm
6 ... 70 mm
Power terminals (supply,
motor, and braking resistor
cables)
N·m (lbf·in)
0.5 ... 0.6 (4.4 ... 5.3)
1.2 ... 1.5 (10.6 ... 13.3)
3 (25)
PE/Ground
Power cable
terminals
clamps
N·m (lbf·in)
N·m (lbf·in)
1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
3 (25)
1.5 (13)
5
2
2
2
Screw lug
(Allen screw)
N·m (lbf·ft)
N/A
N/A
15 (11)
Power
connector
covers
N·m (lbf·in)
N/A
N/A
3 (25)

Publicidad

Tabla de contenido
loading

Tabla de contenido