Cabling examples

ACS850-04-03A0-5...018A-5
3
ACS850-04-025A-5...094A-5
1
3
U1
4
All manuals and user guides at all-guides.com
1
2
2
V1
W1
Cable clamp on bare shield.
1
PE/Ground connection.
2
Between cable clamp and terminals, cover bare
3
shield with insulating tape.
Screw lug detail:
4
Wire sizes accepted by power
terminals
Drive type ACS850-04...
-03A0-5...08A0-5
-010A-5...018A-5
-025A-5...094A-5

Tightening torques

Power terminals (supply,
motor, and braking resistor
Drive type
ACS850-04...
N·m (lbf·in)
-03A0-5...08A0-5
0.5 ... 0.6 (4.4 ... 5.3)
-010A-5...018A-5
1.2 ... 1.5 (10.6 ... 13.3)
-025A-5...094A-5
PE/Ground
Drive type
terminals
ACS850-04...
N·m (lbf·in)
-03A0-5...08A0-5
1.5 (13)
-010A-5...018A-5
1.5 (13)
-025A-5...050A-5
3 (25)
15...22
-061A-5...094A-5
(135...200)
Quick installation guide - ACS850-04
Wire size
2
0.25 ... 4 mm
2
0.5 ... 6 mm
2
6 ... 70 mm
Screw lug
(Allen screw)
cables)
N·m (lbf·ft)
N/A
N/A
3 (25)
15 (11)
Power
Power cable
connector
clamps
covers
N·m (lbf·in)
N·m (lbf·in)
1.5 (13)
N/A
1.5 (13)
N/A
1.5 (13)
3 (25)
1.5 (13)
3 (25)
5