- Example of one wiring diagram .
L1
L2
L3
N
PE
8. Commissioning

8.1 Configuration settings

• X-Care is configured in factory with a set of default value,
ready for use.
• List of available parameters and default values.
Parameters
Type of power supply
Defect post when
• Low speed
• Direction of rotation
• X-Care temperature
• Over-pressure
• Ambient temperature sen-
sor disconnected
CAN bus address
Maximum head
Maximum speed
20
Q1
N
L
X-Care
Range of value
Default value
Mains
Mains
Variable speed
inverter
Setting
Yes
No
No
Yes
Yes
No
Yes
Yes
No
Yes
Yes
No
Yes
Yes
No
OFF
OFF
1 to 64
0 to P max.
P max.
(16 or 25 bar)
(16 or 25 bar)
0 to V max
0
KM1
KM1
U
V
M
SSM
3~
Description
Type of power supply used for dry-run-
ning detection optimization
If yes, dry-contact relay is set when
defect occurred and 'other defect' indica-
tor is turned ON
See "Maximum speed" parameter
Defect occurred when X-Care internal
temperature exceeds 70°C
See "Maximum head" parameter
When OFF, CAN bus is inactive
Over-pressure threshold
Low-speed threshold used to detect any
occured abnormal speed level
W
SALMSON 12/2013