INSTALLATION
30
®
Eaton
9140 (9910-E82/E83) UPS Installation Guide for IBM
www.eaton.com/ibm
NOTE DO NOT protect laser printers with the UPS because of the exceptionally high power
requirements of the heating elements.
NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an
overload alarm.
4.
Plug the equipment to be protected into the UPS output
receptacles, but do not turn on the protected equipment (see
Figure 29).
5.
Make any necessary provisions for cord retention and strain relief.
6.
If an emergency power-off (disconnect) switch is required by local
codes, see "REPO and ROO Installation" on page 31 to install the
REPO switch before powering on the UPS.
If you are not required to install a REPO switch, you can install an
optional remote on/off (ROO) switch (see page 31).
7.
Switch all circuit breakers to the ON (
| ) position.
S
®
Applications
164201715 Rev 2