7.
To configure the UPS for REPO behavior, select MENU from the
system status screen, then select SETUP, USER SETUP, and
CONTACT CONFIG.
Set CONTACT USAGE to REPO. Then set CONTACT TYPE to either
normally-open (N/O) or normally closed (N/C).
8.
To configure the UPS for ROO behavior, select MENU from the system
status screen, then select SETUP, USER SETUP, and
CONTACT CONFIG.
Set CONTACT USAGE to ROO. Then set CONTACT TYPE to either
normally-open (N/O) or normally closed (N/C).
9.
REPO only. Start the UPS by selecting MENU from the system
status screen, then select CONTROL, OUTPUT CONTROL,
UPS TO ONLINE, and OK to confirm.
10. Activate the external REPO or ROO switch to test the function.
Verify the status change on the UPS display.
11. REPO only. De-activate the external REPO switch and restart the
UPS.
®
Eaton
9140 (9910-E82/E83) UPS Installation Guide for IBM
S
®
Applications
164201715 Rev 2
www.eaton.com/ibm
INSTALLATION
33