Configuration

Caution
The CPV Direct contains electronically sensitive com
ponents. The CPV Direct will be damaged if you touch
the contact surfaces of the plug connectors or if you do
not observe the regulations for handling electrostati
cally sensitive components.
Proceed with the configuration as follows:
1. Switch off the power supply.
2. Remove the switch cover.
3. Set the following with the DIL switch: station number,
device−specific diagnostics for DeviceNet.
4. If modules or valve terminals are connected to the
CPI extension connection: Carry out automatic detection
(see section 7).
5. Refit the switch cover.
6. If the CP system is the first or last slave in a field bus
segment, a terminating resistor must be fitted
between the field bus cables (120 , 0.25 W).
Warning
S Check the measures for putting the system into a
safe state in the event of an EMERGENCY STOP.
Further information: manual P.BE−CP−DN3−...
22
Festo CPV...−GE−DN3−8 0709NH English