Burner Start-Up And Adjustment - Ecoflam MAIOR P 150.1 AB Manual Del Usuario

Quemador de gasoleo
Ocultar thumbs Ver también para MAIOR P 150.1 AB:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1 - INLET
2 - RETURN
3 - BLEED AND PRESSURE GAUGE PORT
4 - VACUUM GAUGE PORT
VERIFY:
- That piping system is perfectly sealed;
- That the use of hoses is avoided whenever is possible (use copper pipes preferably);
- That depression is not greater than 0,45 bar, to avoid pump's cavitation;
- That check valve is suitably designed for the duty;
The pump pressure is set at a value of 12 bar during the testing of burners. Before starting the burner, bleed the air in
the pump through the gauge port. Fill the piping with light-oil to facilitate the pump priming.
Start the burner and check the pump feeding pressure. In case the pump priming does not take place during the first
prepurging, with a consequent, subsequent lock-out of the burner, rearm the burner's lock-out to restart, by pushing
the button on the control box. If, after a successful pump priming, the burner locks-out after the prepurging, due to a
fuel pressure drop in the pump, rearm the burner's lock-out to restart the burner. Do never allow the pump working
without oil for more than three minutes. Note: before starting the burner, check that the return pipe is open. An even-
tual obstruction could damage the pump sealing device.
Once having installed the burner, check the following items:
- The burner power feeding and the main line protection fuses
- The correct length of pipes and that the same are sealed.
- The type of fuel, which must be suitable for burner.
- The connection of boiler's thermostats and all the safeties.
- The motor rotation direction.
- The correct calibration of the motor's thermal protection.
When all the above mentioned conditions are checked and accomplished, it is possible to go on with burner's tests.
Power the burner. The control box feeds the ignition transformer and the burner's motor at the same time, which will
run a prepurging of the combustion chamber for about 26 sec.
At the end of prepurging, the control box opens the fuel pump and the 1st stage (Low flame) solenoid valves, the igni-
tion transformer produces a spark and the burner ignites. After a safety interval of 5 seconds and a correct ignition, the
control box turns off the ignition transformer and, 5 seconds later, sets the motorised air damper to its maximum ope-
ning and opens the 2nd stage solenoid valve (High flame). In case of faulty ignition, the control box switches the bur-
ner into safety condition. In order to obtain an optimal combustion, it is necessary adjust the LOW - HIGH flame air
flow, according to the instruction given further on. During such a phase, it will be possible to manually switch between
HIGH ( II ) and LOW ( I ) flame and viceversa, through the High/Low flame switch. At the end of the adjusting
phase, leave the switch in position II (HIGH flame).
The fuel pump feeding pressure, must remain around 12 bar.
I - 1st Stage.
II - 2nd Stage (with an eventual Low/High automatic switching through a further
thermostat connected to the terminal board, as shown by the scheme).
5 - PRESSURE ADJUSTMENT
6 - TO NOZZLE

BURNER START-UP AND ADJUSTMENT

pag.11
LB360 Maior P 150.1/200.1 AB