Electrical Connection - Balluff BTL7-S5 Serie Instrucciones Breves

Ocultar thumbs Ver también para BTL7-S5 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 14
BTL7-S5 _ _ (B)-M _ _ _ _ -A/B/Y/Z(8)-SA360-KA _ _ -ZA10
Micropulse Transducer - Rod Style

Electrical connection

BTL7 standard
Pin
BTL7-S5_ _-...-S115
BTL7-S5_ _B-...-S115
1
+Clk
2
+Data
3
–Clk
4
Not used 1)
5
–Data
6
GND
7
10 to 30 V
8
Not used 1)
1) Unassigned leads can be connected to GND on the controller
side but not to the shield.
2) Communication line
Pin assignment (view of connector pins of
pigtail), 8-pin M12 circular plug
Shielding and cable routing
Defined ground!
The transducer and the control cabinet must be
at the same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect the transducer and controller using a shielded
cable.
Shielding: Copper filament braided, at least 85%
coverage.
Connector version: Shield is internally connected to
connector housing.
Magnetic fields
The position measuring system is a magnetostrictive
system. It is important to maintain adequate distance
between the transducer cylinder and strong, external
magnetic fields.
Cable routing
Do not route the cable between the transducer, controller,
and power supply near high voltage cables (inductive stray
noise is possible).
The cable must be routed tension-free.
Bending radius for fixed cable
The bending radius for a fixed cable must be at least five
times the cable diameter.
www.balluff.com
BTL7 USB
configurable
BTL7-S510-...-S115
BTL7-S510B-...-S115
+Clk
+Data
–Clk
La 2)
–Data
GND
10 to 30 V
Lb 2)
Startup
DANGER
Uncontrolled system movement
When starting up, if the position measuring system is
part of a closed loop system whose parameters have not
yet been set, the system may perform uncontrolled
movements. This could result in personal injury and
equipment damage.
► Persons must keep away from the system's
hazardous zones.
► Startup must be performed only by trained technical
personnel.
► Observe the safety instructions of the equipment or
system manufacturer.
1. Check connections for tightness and correct polarity.
Replace damaged connections.
2. Turn on the system.
3. Check measured values and adjustable parameters
(especially after replacing the transducer or after repair
by the manufacturer). Recalibrate the transducer, if
necessary.
Operating notes
Check the function of the transducer and all associated
components on a regular basis.
Take the position measuring system out of operation
whenever there is a malfunction.
Secure the system against unauthorized use.
EMC characteristics can only be ensured if the
BTL7-S...-ZA10 is completely installed in a
grounded metal housing.
Accessories
PUR cable, 8-wire, shielded, molded
Straight
BKS-S115-PU-_ _
Example with 5 m:
BKS-S115-PU-05
Angled
BKS-S116-PU-_ _
english
3

Publicidad

Tabla de contenido
loading

Tabla de contenido