• Before wiring the connector (3), unscrew and remove the central screw (2). Use the proper cable terminals (see figures
below). NOTE: Connector (3) wiring must be do ensuring a product rating of IP65;
• Wire the connector (3) with 3x0.75mm² cable for external Ø 6.2 to 8.1 mm. The cable to be used must be in double sheath,
suitable for outdoor use, with a minimum voltage of 500V and a temperature of at least 60 °C;
• Connect terminals 1 and 2 to the power supply and the earth cable to terminal ;
• Secure the connector (3) to the coil (4), tightening (recommended tightening torque 0.4 N.m ± 10%) the clamping screw (2);
• The valve needs to be connected to earth either through the pipe or through other means (ex. cable jumpers).
3.3 - INSTALLATION IN PLACES WHERE THERE IS THE RISK OF EXPLOSION (DIRECTIVE 2014/34/EU)
The solenoid valve is not suitable for use in zones here there is the risk of explosion.
3.4 - GENERIC EXAMPLE OF AN INSTALLATION
1. M16/RM N.A. Manual reset solenoid valve
2. SM jerk ON/OFF valve
3. FM gas filter
4. OPSO series MVB/1 MAX shut off valve
5. RG/2MC pressure regulator
external roof
10
1
M16/RM N.A. - MBA/RM N.A.
9
8
2
6. MVS/1 relief valve
7. Pressure gauge and relative button
8. Gas detector
9. SM remote jerk ON/OFF valve lever control
10. Compensation/Vibration damping joint
internal thermal unit
3
4
5
12
Madas Technical Manual - REV. 0 of 10
discharge in open air
6
7
Oct 2018