2.
Securely fasten enclosure to the mounting location, then attach into conduit system.
3.
If remote indicating systems are used, be sure they comply with NEC requirements,
ensure grounding continuity, and are within electrical ratings listed on the Field
Wiring Diagram.
! CAUTION
Hammers or prying tools must not be allowed to damage the flat ground joint
surfaces or cover gasket.
! CAUTION
Clean both ground joint surfaces of body and cover before closing. Dirt or foreign
material must not accumulate on flat ground joint surfaces. Surfaces must seat
fully against each other to provide a proper explosionproof seal.
4.
Open cover for access to terminal block. Attach field wiring to terminal block and to
additional green ground lug, following the wiring pattern established for your system
and the Field Wiring information contained in this instruction sheet.
5.
Check wiring for correctness with continuity tester and for unwanted grounds with
insulation resistance tester.
6.
Close cover and tighten all cover bolts, torque to 15-20 ft. lbs. (20.3-27 .1 N-m).
! WARNING
Make sure wire casing is safely tucked into enclosure before closing EGL cover.
SUFFIX
S883 ONLY
SUPPLY POWER CONNECTIONS
PRIMARY
LINE 1
VOLTAGE
CONNECTION
TRANSFMR
440/480
WIRE #3
TRANSFMR
WIRES
220/240
#3 & #4
TERMINAL
110/120
BLOCK 1
ARRANGE WIRES TO
CAUTION:
AVOID DAMAGE WHILE CLOSING COVER.
IF 1879 • 03/19
WIRING DIAGRAM - EGL210 - MODEL M6
SUFFIX
R11 ONLY
HEATER
TRANSFMR
WHITE
BLACK
BLK
LINE 2/N
CONNECT
CONNECTION
TRANSFMR
TRANSFMR
WIRES
WIRE #2
#1 & #4
TRANSFMR
WIRES
-
#1 & #2
TERMINAL
-
BLOCK 2
EGL210 GROUND INDICATOR FIELD WIRING
FIGURE 2 - WIRING DIAGRAM
Copyright © 2019, Eaton's Crouse-Hinds Division
Before assembling any mating threads, make certain that there is no dirt or
other foreign material on, or in, either set of threads.
Conduit(s) and any plug(s) threads must be engaged properly with their
mating threads and securely tightened.
All threaded joints in the enclosure have been treated at the factory with
Eaton's Crouse-Hinds series STL screw thread lubricant, which acts as
a lubricant and anti-seize agent. Whenever any threaded joint(s) are
disassembled, the threads should be re-treated with STL and care must be
exercised in mating threads properly, and securely tightening the threaded
joints.
NOTES
1.
For standard 120V supply voltage, connect leads directly to terminals: "1" for power,
"2" for neutral, "3" for ground. The additional ground wire must be attached to
the green wire lug, which is factory installed in the enclosure. For 240 or 480 volt
control voltages, connect leads directly to the transformer as marked.
2.
Terminals 4, 5, 6, 7 , 8 and 9 on the terminal block are connected to the control relay's
contacts and are to be used for connections to remote indicators or control circuits.
The electrical ratings for the relay's contacts are given on the field wiring diagram.
Terminals 4 and 5 and 7 and 8 are normally open. Terminals 4 and 6 and 7 and 9 are
normally closed.
BLK
1
WHT
2
MTL5516C
-
SWITCH AMPLIFIER
4
5
-
MPA5500
PWR SUPPLY
WHT
GRY
1
3
4
5
6
7
2
2
GRY
YEL
4
2
RELAY
COIL
BLU
1
3
BLK
! CAUTION
BLK
7
BLK
8
BLK
9
10
RED
BLK
11
GRN
13
14
12
L
N
PUR
8
9
DIP SWITCH SETTINGS
BRN
6
8
5
7
RED
ORG
WHT
R
WHT
G
ON
CH1
PR •
OFF
LF •
OFF
PR •
ON
LF •
OFF
CH2