Valve body
Max. working pressure:
Medium peak temperature:
specification
Max. differential pressure:
Connections:
Bottom 3-way connection:
ctuator
Power supply:
specification
(The higher power value of 11 W relates to the pick-up during the opening
phase and the lower one of 4 W represents the holding value absorbed
with the valve open).
Capacity of the auxiliary microswitch contacts:
Protection class code Nr. 6300.:
Protection class
Opening time:
Closing time:
Maximum ambient temperature:
Maximum wire temperature:
Conforms to Normes/Directives:
Supply cable:
mbient
Medium working temperature range:
conditions
Nell'installazione in cassette occorre lasciare uno spazio sufficiente fra
Installazione
comando e telaio per una eventuale manutenzione o sostituzione. Nel
Installation
montaggio della valvola sull'impianto si deve rispettare il senso del fluido
Einbau
indicato sul corpo. La valvola non va mai collegata con lo stelo rivolto
Mise en place
verso il basso. Durante la messa in servizio della valvola è opportuno
Instalación
simulare le funzioni di comando agendo sul termoregolatore. Per la
Instalação
verifica del funzionamento occorre attendere alcuni minuti essendo il
Installatie
servocomando a funzionamento lento (da 1,5 a 3 minuti). nche in caso
di smontaggio della testina procedere dopo almeno 3 minuti dal momento
che si è interrotto il collegamento.
When installing the equipment in a box sufficient space must be left
between the actuator and frame so that maintenance work and
replacements can be carried out. When fitting the valve to the system the
direction of the fluid shown on the body must be observed. The valve is
never connected with the stem turned downwards. When the valve is put
into operation, it is advisable to simulate the control functions by
operating the thermoregulator.
checking the operation as the actuator operates slowly (from 1,5 to 3
minutes). When dismantling the head also wait for at least 3 minutes from
the time that the connection is interrupted before proceeding.
bsorbed power:
code Nr. 6301.:
mbient temperatures: - Operation:
230 V or 24 V (+10% -15%) - 50 Hz
IP 42 - IP 44 (in vertical position)
0–55°C EN 60721-3-3 Class 3K3
- Transport:
-20–70°C EN 60721-3-2 Class 2K3
- Storage:
-5–50°C EN 60721-3-1 Class 1K2
few minutes must be allowed for
2
100 kPa (10,2 m w.g.)
Ø 1/2" , 3/4", 1", with union
max 11 W
120–180 s
90–150 s
EN 60730-1 • EN 60730-2-14
2014/35/CE • 2014/30/CE
4x0,75 mm
2
- lenght 90 cm
2x0,75 mm
2
- lenght 90 cm
max. umidity 85%
max. umidity 95%
max. umidity 95%
10 bar
110°C
3/4" F
6 (3)
IP 20
55°C
80°C
-5–80°C