Attaching the hanging bracket
fi rst
1
Remove the screws fastening hanging
onto the indoor unit.
Screw
Hanging bracket
2
Loosen the bolts fastening hanging bracket
onto the indoor unit and remove the hanging
bracket.
Bolts for fastening the hanging
bracket (Loosen these bolts.)
3
Adjust the length of the two bolts for fastening
the hanging bracket, as shown below.
0.3" (7) to
0.5" (12)
Indoor Unit
Adjust the length of the bolts for
fastening the hanging bracket.
4
Fasten the hanging bracket with the hanging
bolts and ensure that the bracket is level from
front to back and from side to side.
Hanging bolt
(locally procured)
Hanging bracket fi xing board
Washer
N
Ceiling surface
(Accessory)
(inside dimension)
Double nut
(locally procured)
Front
(Unit : in (mm))
Model MMC-
N
AP018
34.2" (867) to 34.3" (872)
AP024, AP030
46.7" (1184) to 46.9" (1189)
AP036, AP048
59.1" (1501) to 59.3" (1506)
21-EN
1115652706_01_EN.indd 11
1115652706_01_EN.indd 11
5
Attach the indoor unit onto the hanging
bracket and fasten it tight with the bolts and
screws.
bracket
Bolts for fastening the hanging bracket
(Fasten the bolts tight.)
Use bolts to fasten the
hanging bracket.
CAUTION
The ceiling is not always level. Use the level gauge
to measure the level of the ceiling in the width and
depth directions. Adjust the bolts for the hanging
brackets so that the level error will be within
0.2" (5 mm).
Do not lower the air discharge side and the side
opposite to the selected drain pipe withdraw.
– 11 –
Installation of plate conduit A (Option accessory group 01)
Super Modular Multi System u series (SMMS-u)
REQUIREMENT
For support electric wiring Super Modular Multi System u series (SMMS-u)
1
Removal of plate conduit A (Group 02).
1) Remove the grommet from plate conduit A (Group 02).
2) Remove the screws of plate conduit A (Group 02) (5 positions).
3) Remove the plate conduit A (Group 02).
Plate conduit A (Group 02)
2
Installation of plate conduit A (Group 01).
1) Prepare plate conduit A (Group 01) from accessory.
2) Installation plate conduit A (Group 01) at unit fix by screws (5 positions).
3) Installation grommet at plate conduit A (Group 01).
Grommet
Grommet
Plate conduit A (Group 01)
22-EN