2.4.
Connector features
The control unit is connected to the kiln via a 14-pin connector.
Features:
• CPC 14 connector
• 14-pin screw connection
• Bayonet fitting
The black 14-pin socket provided for this is located on the switch cabinet of the kiln (near the electrical supply line).
CPC 14 kiln socket
2.5.
Plug pin assignment
Pin no.
X = Used
1
X
2
X
3
−
4
−
5
−
6
−
7
X
8
X
9
X
10
−
11
−
12
X
13
X
14
X
Note:
The wiring of the mating CPC 14 socket can vary between kiln manufacturers!
2.6.
Kiln contactor protection circuit
The coil of each kiln contactor should be suppressed with an RC circuit. RC circuits must be connected directly across the
coil terminals on each contactor. ROHDE kilns are delivered this way as standard. For kilns from other manufacturers,
suitable products are available as accessories from contactor manufacturers.
CPC 14 controller plug
Description
Thermocouple 1 +
Thermocouple 1 -
Not used
Not used
Not used
Not used
Additional switch output (230 V)
L1 feed 230 V AC
N feed
Not used
Not used
Safety contactor switch output
Neutral conductor switch output
Zone 1 switch output
47 / 280
Pin assignment