T-Series Energi Savr Node

Product overview

A T-Series Energi Savr Node system consists of T-Series Energi Savr Node (ESN) units, a Quantum Hub, Lutron T-Series LED drivers, inputs,
wallstations, and QS devices. The diagram on the previous page shows an example of control inputs that are part of a system.
• T-Series ESN units are powered by line voltage (Hot and Neutral).
• The T-Series ESN unit has inputs for:
– 4 Lutron daylight sensors (model: EC-DIR-WH)
– 4 Lutron occupant sensors (models: Lutron LOS series)
– 4 Lutron infrared (IR) receivers (models: EC-DIR-WH, EC-IR-WH, PX-2B, PX-2BRL, PX-3B, PX-3BRL)
– 1 contact closure input (CCI)
– 1 emergency contact closure input (defaults to Emergency Mode in the absence of a contact closure across the input)
• The QS Link can have up to 100 zones and 100 QS devices.
• The T-Series ESN unit counts as 1 QS device and 1–100 zones on the QS link (depending on system programming).
• A system can have a maximum of 100 wired or wireless daylight sensors, 100 wired or wireless occupancy sensors, and 100 wired or
wireless controllers (Pico wireless controllers, IR receivers, or QS wallstations).
• The T-Series ESN unit supplies up to 30 Power Draw Units (PDUs) for powering accessory QS devices and sensors/controls wired to QS
Sensor Modules (QSMs). Refer to accessory device documentation for power draw information.
Refer to the following step-by-step guide for proper T-Series ESN unit installation.

Wiring overview

H/L
N
N/C
LOOP 2
LOOP 1
LOOP 2
RESET
LOOP 2
LOOP 1
PWR
TEST
TEST
TEMP
LOOP 1
QS LINK
GROUP 1
GROUP 2
GROUP 3
GROUP 4
CONTACT CLOSURE
ETHERNET
PWR
TEST
TEST
TEMP
QS LINK
QS
Link
Lutron
2
|
|
Installation Guide
H/L
N
N/C
Control
power
H/L
N
GROUP 1
GROUP 2
Inputs
LOOP 2
LOOP 1
PWR
TEST
TEST
TEMP
N/C
GROUP 3
GROUP 4
CONTACT CLOSURE
CCI
Contact
LOOP 2
LOOP 1
T-Series
digital links
LOOP 2
LOOP 1
ETHERNET
Emerg
Ethernet Jack
RESET
(do not use or
connect to internet)
Closure
Inputs