T-Series Energi Savr Node
Step 5: Contact Closure Inputs: Emergency and
CCI
WARNING: Shock Hazard. May result in serious injury
or death. Do not wire when live. Turn off power to all
power feeds via circuit breaker or isolator before wiring or
servicing.
• Contact Closure (Emergency and CCI) wiring is IEC PELV / NECR
Class 2. Follow all applicable national and local codes for proper
circuit separation and protection.
• CCI input must be used with dry contact closure devices.
• Emergency input is normally closed (NC). The T-Series ESN unit is
shipped with a jumper pre-installed.
• If the Emergency input is open, the T-Series ESN unit will enter
Emergency Mode, which will force all ballasts and/or drivers to their
emergency level (100% by default) and disable control from inputs
and QS devices. When the closure is restored, ballasts and/or drivers
will return to their previous level.
Note: The T-Series ESN unit will default to Emergency Mode if the
Emergency input is left open. If no Emergency contact input is
required, please leave the wire jumper in the Emergency input
terminals.
Lutron
6
|
|
Installation Guide
Contact Closure Wiring
CCI – Contact Closure Input
• 20 AWG to 12 AWG (0.5 mm
• Strip length: 1/4 in (6 mm)
• Torque: 5 in-lb (0.5 N
COM – Common
to 4.0 mm
2
m)
T-Series Energi Savr Node
COM – Common
EMERG – Emergency
)
2
Installation Guide