Step 4: Input group wiring
To connect a daylight sensor, occupant sensor, or IR receiver, refer to the instruction sheets provided with the devices. The diagram for the
input terminals is shown below.
WARNING: Shock Hazard. May result in serious injury or death. Do not wire when live. Turn off power to all power feeds via
circuit breaker or isolator before wiring or servicing.
Buttons and LEDs in the unit are used for troubleshooting. If wiring is exposed when accessing buttons and LEDs, the unit must
be accessed by a certified electrician, following local codes.
Note: The T-Series ESN unit accepts only one IR input (either daylight sensor, IR sensor, or IR receiver) per group.

Input Group Wiring

H/L
N
N/C
LOOP 2
LOOP 1
LOOP 2
LOOP 1
PWR
TEST
TEST
TEMP
QS LINK
GROUP 1
GROUP 2
GROUP 3
GROUP 4
CONTACT CLOSURE
ETHERNET
20 V: 20 V
• 22 AWG to 12 AWG (0.5 mm
• Strip length: 1/4 in (6 mm)
• Torque: 5 in-lb (0.5 N
m)
* Only one IR device may be connected per input. If the IR signal from a daylight sensor is
connected, an IR receiver can not be connected to the same input, and vice-versa.
** Connect the gray wire on -R model occupancy sensors.
T-Series Energi Savr Node
NOTE: There are four input groups. Each group has the
same inputs as shown in the diagram below.
RESET
Group 1 shown
Com: Common
IR: IR Receiver*
Daylight: Daylight Sensor
Occ: Occupancy Sensor
Note: Maximum wire run length to each
input not to exceed 100 ft (30.4 m).
to 4.0 mm
)
2
2
IR Transmitter
Installation Guide
T-Series Energi Savr Node
Daylight/
IR Sensor*
English
Español
|
Installation Guide
Group 2 shown
Occupancy Sensor
IR Transmitter
Français
IR Receiver*