Modbus control
To make this limitation permanent, set the
desired value in the Modbus register 40349.
To disconnect the inverter immediately from the
utility grid while the Limited Export function is
running, set the value "0" in the Modbus
register 40348.
or further information on the Modbus interface
see technical information
"SUNNY TRIPOWER 60 /
SUNNY HIGHPOWER PEAK1 - SunSpec®
Modbus® Interface" at www.SMA-Solar.com.
igure 25: eeding-in operation with Limited Export / Peak Load Shaving
Installation Manual
5 LCS-Tool
IMVIOBOX-IA-xx-18
35