5.2.4 Setting the System Fallback
Figure 19: LCS-Tool - setting the fallback parameter
A system fallback can be configured in the event of a
communication failure between the Inverter Manager and a
superior control unit (e.g. SCADA system or
Power Plant Controller). The superordinate system fallback
can only be configured via the LCS-Tool. To set the values
for a superordinate fallback, use your SMA Grid Guard
code under the user group Installer (see
section 5.2.2, page 21).
Procedure:
1. Open the LCS-Tool.
2. Log in as an Installer.
3. Call up the menu Setup.
4. Enter the respective values under Plant fallback.
5. Select [Save] to save the changes.