Omron VARISPEED F7 Guía De Referencia Rápida página 21

Ocultar thumbs Ver también para VARISPEED F7:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 50
Param-
eter
Name
Num-
ber
Torque Limit (only OLV and CLV)
Forward drive
L7-01
torque limit
Reverse drive
L7-02
torque limit
Forward
L7-03
regenerative
torque limit
Reverse
L7-04
regenerativ
torque limit
Monitor Data
U1-01 Frequency reference in Hz / rpm
U1-02 Output frequency in Hz / rpm
U1-03 Output current in A
U1-06 Output voltage in VAC
U1-07 DC bus voltage in VDC
U1-08 Output power in kW
U1-09 Torque reference
Input terminal
U1-10
status
Output termi-
U1-11
nal status
Operation
U1-12
status
U1-13 Cumulative operation time in hrs.
U1-21 ASR input
U1-22 ASR output
U1-34 OPE fault parameter
U1-40 Cooling fan operating time in hrs.
EN-20
Description
Sets the torque limit vlaue as a per-
centage of the motor rated torque.
Four individual regions can be set.
Output torque
Positive torque
No.
motor
Regen.
Reverse
rotations
Forward
Regen.
Negative torque
Shows input ON/OFF status.
U1-10 =
1: FWD command
(S1) is ON
1: REV command
(S2) is ON
1: Multi input 1
(S3) is ON
1: Multi input 2
(S4) is ON
1: Multi input 3
(S5) is ON
1: Multi input 4
(S6) is ON
1: Multi input 5
(S7) is O N
Shows output ON/OFF status.
U1-11 =
1: Multi-function
contact output 1
(M1-M2) is ON
1: Multi-function
contact output 2
(M3-M4) is ON
1: Multi-function
contact output 3
(M5-M6) is ON
Not used
(Always 0).
1: Error output
(MA/MB-MC) is ON
Inverter operating status.
U1-12 =
Run
1: Zero speed
1: Reverse
1: Reset signal input
1: Speed agree
1: Inverter ready
1: Minor fault
1: Major fault
Param-
eter
Name
Num-
ber
Fault Trace Data
U2-01 Current fault
U2-02 Last fault
U2-03 Reference frequency at fault
U2-04 Output frequency at fault
U2-05 Output current at fault
o
U2-07 Output voltage reference at fault
U2-08 DC bus voltage at fault
U2-09 Output power at fault
U2-11 Input terminal status at fault
U2-12 Output terminal status at fault
U2-13 Operation status at fault
U2-14 Cumulative operation time at fault
Fault History Data
U3-01
to
Last fault to fourth last fault
U3-04
U3-05
to
Cumulative operation time at fault 1 to 4
U3-08
U3-09
to
Fifth last to tenth last fault
U3-14
U3-15
to
Accumulated time of fifth to tenth fault
U3-20
* The following faults are not recorded in the error log:
CPF00, 01, 02, 03, UV1, and UV2.
Digital Input Function Selections (H1-01 to H1-05)
3
Multi-step speed reference 1
4
Multi-step speed reference 2
5
Mulit-step speed reference 3
Jog frequency command (higher priority than multi-
6
step speed reference)
7
Accel/decel time selection 1
F
Not used (Set when a terminal is not used)
14
Fault reset (Reset when turned ON)
19
PI control disable
External fault; Input mode: NO contact/NC contact,
20 to
2F
Detection mode: Normal/during operation
71
Speed/torque control change (ON: Torque control)
77
Speed control (ASR) gain switching (ON: C5-03)
Digital Output Function Selections
(H2-01 and H2-02
During run 1 (ON: run command is ON or voltage is
0
being output)
Inverter operation ready; READY: After initialization or
6
no faults
F
Not used. (Set when the terminal is not used.)
10
Minor fault (Alarm) (ON: Alarm displayed)
1A
During reverse run (ON: During reverse run)
Motor overload (OL1, including OH3) pre-alarm (ON:
1F
90% or more of the detection level)
During torque limit (current limit) (ON: During torque
30
limit)
Activated if the ASR is operating for torque limit. The
32
ASR output becomes the torque reference, the motor
is rotating at the speed limit.
Description

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cimr-f7z

Tabla de contenido