Event Logging
This submenu allows the user to view the extreme values of some key parameters.
Meter
This function offers a possibility for the user to display three most concerned
measurements in one screen. For instance, three line voltages can be shown in one
screen in a better resolution and better view. Detailed instructions for this function can
be found in
4.2.4.
4.2.1
Overview
Details on all available measurements through RVT:
Designation
Unit
Voltage
Vrms
V
V1
V
Frequency
Hz
THDV
%
V harm. Table
V harm. chart
Current
Irms
A
I1
A
THDI
%
I harm. table
I harm. chart
Power
Cos j
PF
P
W
Q
var
S
VA
Table 1: Measurements overview
Description
Rms Voltage
Rms voltage at the
fundamental frequency
Fundamental voltage
frequency
Total harmonic voltage
distortion on voltage
Voltage harmonics displayed
in a table
Voltage harmonics displayed
in a bar graph
Rms Current
Rms current at the
fundamental frequency
Total harmonic current
distortion on current
Current harmonics displayed
in a table
Current harmonics displayed
in a bar graph
Displacement power factor
Power factor
Active power
Reactive power
Apparent power
Range
Accuracy
Up to 690Vac
± 1 %
Up to 690Vac
± 1 %
45Hz - 65Hz
± 0.5%
0 - 300%
± 1 %
2nd-49th
See later in this paragraph
2nd-49th
See later in this paragraph
Range
Accuracy
0 - 5 A
± 1 %
0 - 5 A
± 1 %
0 - 300%
± 1 %
2nd-49th
See later in this paragraph
2nd-49th
See later in this paragraph
Range
Accuracy
-1 è +1
± 0.02
-1 è +1
± 0.02
-10
9
9
W
± 2%
è10
-10
9
9
var
± 2%
è10
9
0 è10
VA
± 2%
Power Factor Controller RVT ç Measurements and Settings 25
Max value
6
10
V
6
10
V
45Hz - 75 Hz
1000 %
Max value
6
10
A
10
6
A
1000%
Max value
-1 è +1
-1 è +1
-10
9
9
W
è10
-10
9
9
var
è10
9
0 è 10
VA