Note 1: the RVT is self-protected against an internal over-temperature of 85°C. The
actions described above will occur when the internal temp exceeds this protection level.
The RVT will restart automatically when the internal temperature falls back below 80°C.
Note 2: the temperature protection levels are disabled by default. When a level is entered,
the RVT checks one of the eight probe connections.

4.3.1.5 Restore default settings

Start screen->Settings->Manual settings->restore default set.
By selecting and validating the "Restore default set." item, all the values of the RVT
parameters are reset to their default values (see separate document joined with the
RVT), except if the bank settings item is locked, in that case the bank settings are not
changed.
Warning: important parameters may be lost.
Comment: before restoring default settings, please make sure that:
-
RVT is unlocked (description in paragraphs
-
RVT is in SET mode (description in paragraph 3.2.2.)
4.3.2

Commissioning (SET mode)

This sub-menu allows the user to do a complete automatic commissioning or a guided
commissioning of the controller.
50 Measurements and Settings ç Power Factor Controller RVT
Figure 44: RVT restore default settings