4 Additional information

4.1 Ramp Control description
System control uses fixed ramps to regulate system variable to follow setpoint as described below.
Ramps can be set to one of the preset values:
• Slow: big pump size
• Medium: medium pump size
• Fast: small pump size
Ramp time
Ramp 1
Up
Fast
4
Medium
6
Slow
8
The ramp is expressed in seconds and represents the time needed for the motor to go from 0 Hz to the maxi-
mum frequency, or from maximum frequency to 0 Hz.
Ramp 1 (up or down) is always used below minimum frequency/sleep frequency and when feedback value is
outside the regulation band.
Ramp 2 (up or down) is used when feedback value is inside the regulation band.
The motor control will use the ramp-up (1 or 2) till the feedback value reaches the upper limit of the regula-
tion band. Once the upper limit is reached, the motor control will use the ramp-down (1 or 2) till the feed-
back value reaches the lower limit of the regulation band.
Parameter
34
Protocol
Address
1
Baud Rate
9600
No
Booster
Ramp 2
Down
Up
4
70
6
70
8
70
3–41
3–42
3–51
2. Select the communication protocol
3. Select the address
4. Select the Baud Rate
5. Select the network configuration
6. Select No to exit
Ramp 1
Down
Up
70
8
70
12
70
16
Description
Ramp 1 Ramp Up Time
Ramp 1 Ramp Down Time
Ramp 2 Ramp Up Time
HVAC
Ramp 2
Down
Up
8
90
12
90
16
90
Down
90
90
90