Parameters In The Temperature Switch Digital Display - Parker Controller Family Manual De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

7.1

Parameters in the temperature switch digital display

Menu settings for the switching output
Password is preset. You can change to the programming mode
PAS
only after entering the correct digits.
The programming mode for the switching output:
S1
S1 = switching output 1
S2
S2 = switching output 2
(This menu does not function when S2 is set as the error output)
Switching point (SP): the upper temperature limit, at which the
SP1
switching output changes its state.
SP2
SP1 = switching output 1; input as temperature value
SP2 = switching output 2; input as temperature value
Reverse switching point (rSP): the lower temperature limit, at
rSP1
which the switching output changes its state.
rSP2
rSP1 = Reverse switching point (rSP1) of switch output 1;
Input as temperature value
rSP2 = Reverse switching point (rSP2) of switch output 2;
Input as temperature value.
The reverse switching point is always lower than the respective
switching point.
If the reverse switching point is set higher than the switching
point, the reverse switching point will automatically be lowered
by 0.75°C (0.5% of 150°C) from the switching point. The
warning message Att (Attention) appears, which must then be
cleared by pressing Enter