Display: value shown on the digital display during run mode.
diS
Act = actual system pressure
Min = mimimum system pressure
MA = maximum system pressure
SP1 = switching point 1
SP2 = switching point 2
OFF = off indication
Configuration of analogue outputs
AnA
0-20 = 0-20mA
4-20 = 4-20mA
Calibration of starting value (0 or 4 mA) for the analogue
FroM
output.
Adjustable from -50 °C to 150 °C
Example for AnA = 0-20:
0000 = at 0 °C the analogue output yields 4 mA.
The starting value is always lower than the end value.
If the starting value is set higher than the end value, the start-
ing value will automatically be reset 0.75°C (0.5% of 150°C)
lower than the end value. The warning message Att (Attention)
appears, which must then be cleared by pressing Enter
Calibration of the end value (20 mA) for the analogue output.
to
Adjustable from -50 °C to 150 °C
0150 = at 150 °C the analogue output yields 20 mA.
Deleting the minimum and maximum values in memory.
rES
YES = yes, clear memory now
no = no; do not clear memory now
98
.