Parameters in the level switch digital display

Menu settings for the switching output
Password is preset. You can change to the programming mode
PAS
only after entering the correct digits.
The programming mode for the switching output:
S1
S1 = switching output 1
S2
S2 = switching output 2
(This menu does not function when S2 is set as the error
output)
Switching point (SP): the upper level limit, at which the switch-
SP1
ing output changes its state.
SP2
SP1 = switching output 1; input as level value.
SP2 = switching output 2; input as level value.
Reverse switching point (rSP): lower level limit,
rSP1
at which the switching output changes its state.
rSP2
rSP1 = Reverse switching point (rSP1) of switch output 1;
Input as level value (e.g. 80 % or 90 mm).
rSP2 = Reverse switching point (rSP2) of switch output 2;
Input as level value (e.g. 5 % or 75 mm).
If the switching point is set lower than the reverse switching
point, the reverse switching point will automatically be reset to
a value 5 mm lower than the switching point.
The warning message Att (Attention) appears, which must
then be cleared by pressing Enter .