• ANTIFREEZE FUNCTION
CONFIGURATION
The power board enables you to select two types
of operation that can be activated by means of the
on-board display:
• "nonE" function - Without preheating (default)
• "HEAt" function - With preheating
From the main menu, access the "TECH" menu
and press the "+" key to display the "FrSt" menu.
Then press "Enter" to confirm.
Using the "+" key, choose either the nonE or HEAt
function.
Confirm the selected function with the "Enter" key.
PLEASE NOTE: By default the HEAt function con-
trols the modulating ducted electric resistance
supplied as an accessory.
In order to control an anti-freeze system with
hydronic preheating coil, the setting FrSt-->
HEAt must be associated with the specific menu
configuration "DGTO" which sets a digital output
signal, contact "3-4" of the power board (see POW-
ER BOARD diagram).
FRSt
ENTER
NO*= normally open contact
NC*= normally closed contact
78
NonE
ENTER
HEAt
ENTER
• DRY CONTACT C1-C1
CONFIGURATION
IMPORTANT!:
The function is available by
connecting the dry contact C1-C1 on the power
board.
The dry input contact (NO
types of operation that can be activated from the
on-board display:
• Remote On/Off "trnF" function (default)
unit Off when the contact is closed
• Booster "bSt" function
Booster function active when the contact is
closed.
From the main menu, access the "TECH" menu
and press the "+" key to display the "C1C1" menu.
Then press "Enter" to confirm.
Using the "+" key, choose either the trnF or bSt
function.
Confirm the selected function with the "Enter" key.
C1C1
ENTER
ATTENTION!: in case of units supplied
without T-EP you are recommended
to use the ON-OFF REMOTE CONTROL
FUNCTION
*
) C1-C1 enables two
tRnF
ENTER
bst
ENTER