• DGTO DIGITAL OUTPUT SIGNAL
CONFIGURATION
There are three configurations available for man-
aging the digital output signal:
• "COnS" function (default) - Digital ON/OFF
enabling signal
• "Post" function - Post Treatment with hydronic
coil
• "PrE" function - Antifreeze Pre Treatment with
hydronic coil
From the main menu, access the "TECH" menu
and press the "+" key to display the "DGto" menu.
Then press "Enter" to confirm.
Using the "+" key, choose either the COnS, Post
or PrE function.
Confirm the selected function with the "Enter" key.
dGto
ENTER
80
ConS
ENTER
Post
ENTER
PrE
ENTER
• SERIAL PORT RS485-A DATA
TRANSMISSION
SPEED CONFIGURATION
Depending on the specifications of the Mod-
bus supervision system that interfaces with the
electronic board, there are two different config-
urations available for setting the data exchange
speed via serial port RS485-A:
• "Std" (default) - 9600 bps
• "UP" - 38400 bps
From the main menu, access the "TECH" menu
and press the "+" key to display the "Nbsp" menu.
Then press "Enter" to confirm.
Using the "+" key, choose either the Std or UP
function.
Confirm the selected function with the "Enter" key.
NbsP
ENTER
• SETTING THE SERIAL NETWORK
ADDRESS
It is important for every unit to have a unique
address when a MODBUS unit network is set up,
so that the software can recognise and manage it.
It is important for more units forming part of the
same network not to be named with the same
address.
The address number is set using the "NbAd" func-
tion.
From the main menu, access the "TECH" menu
and press the "+" key to display the "NbAd" menu.
Confirm with the "Enter" key.
Using the "+" key, select the address number to
be associated with the unit.
Confirm the selection with the "Enter" key.
NbAd
ENTER
std
ENTER
Up
ENTER
1
ENTER