• COMMISSIONING
Once the unit has been installed
and powered and the T-EP con-
troller has been connected, it is
possible to SET THE FAN AIR FLOW RATE.
TECHNICAL"
"
TECHNICAL
The "
used by the installer or by qualified
personnel.
Once the unit has been installed and
powered, the air flow rate must be set.
Before carrying out the calibration, the fans are
set to the default flow rate.
ATTENTION: If no flow rate calibration procedure
is carried out, the machine will operate using the
default flow rate as the calibration flow rate for
both fans. The default flow rate corresponds to the
reference value with respect to EU Reg. 1253/14 and
is equal to 91 m 3 /h.
• SETTING THE FAN AIR
FLOW RATE
1. Turn the unit on from the ON/OFF key on the
display.
2. Press the ON/OFF and "M" Menu keys at the
same time to access the TECHNICAL MENU.
88
MENU
" menu must only be
3. Use the TOUCH PAD to select the installer
menu
.
Press the Enter key to confirm
Select the "V" symbol and confirm
The message V1 flashes;
Perform the setting of fan V1;
access the menu by pressing enter, the display
shows:
V
V
Press the Enter key to confirm
For fan V2, the same flow rate set for fan "V1" is
suggested by default.
To differentiate the extraction fan "V2" from intake
fan "V1", repeat the same procedure for setting the
flow rate described for "V1".
The controller displays flashing " V2 ";
confirm with the enter
V
V
When fan V2 has been set as well, go back to the
main screen by pressing "M"
.
.
set the nominal project
flow rate (m
3
/h) from
the TOUCH PAD
_
.
key.
set the nominal project
3
flow rate (m
/h) from the
+
TOUCH PAD
.
_
3 times.
+
.