SITRANS LR 400 Wiring Requirements

All field wiring must have insulation suitable for the applied input voltage
4-20 mA, Profibus-PA, dc input circuits, 14-20 AWG, shielded copper wire
ac input circuit, minimum 14 AWG copper wire
Recommended torque on terminal clamping screws, 0.5-0.6 Nm
The 24 Vdc version must only be connected to SELV or PELV circuits.

SITRANS LR 400 Wiring

ac
Hart Wiring
cable clamp
4 5
3
6
7 8
Rated temperature of
connection cables must
mA
exceed maximum ambient
temperature by at least 15 K
dc
Hart Wiring
cable clamp
3
4 5
6
7 8
Rated temperature of
connection cables must
mA
exceed maximum ambient
temperature by at least 15 K

Functional Dimensions

Parameters:
1.3
Nozzle height
4.2.2.3 Dead band
1.6
Lower range value (LRV)
1.5
Upper range value (URV)
1.4
Vessel height
Page EN-4
SITRANS LR 400 – QUICK START MANUAL
earth
terminal
1 2
L
L
1
2
N
earth
terminal
1 2
19-30 V
100%
0%
Profibus Wiring
cable clamp
3
4 5
6
7 8
Rated temperature of
connection cables must
PROFI-
exceed maximum ambient
BUS PA
temperature by at least 15 K
Profibus Wiring
cable clamp
3
4 5
6
7 8
Rated temperature of
connection cables must
PROFI-
exceed maximum ambient
BUS PA
temperature by at least 15 K
1.3
1.4
1.5
1.6
earth
terminal
1 2
L
L
1
2
N
earth
terminal
1 2
19-30 V
4.2.2.3
7ML19985QN81